How to read a Rosemount 3051 model code
A Rosemount 3051C model code is a string of fixed positions followed by option codes. Each position fixes one property of the transmitter. This page lists the positions and their common codes as published in the Emerson product data sheet for the Rosemount 3051, and decodes one example.
WhatsApp: +34 655 099 909Updated: November 2026
Reply within 4 business hours.
Quotations are free and carry no obligation. * required.
We use your details only to answer this request. Privacy.
sourcing@alisios.co · WhatsApp
What does each position in a Rosemount 3051C model code mean?
| Position | What it fixes | Common codes |
|---|---|---|
| 1 | Model | 3051C = Coplanar pressure transmitter |
| 2 | Measurement type | D = differential, G = gage, A = absolute |
| 3 | Pressure range | 0 to 5 (see the range table below) |
| 4 | Transmitter output | A = 4–20 mA with HART, F = FOUNDATION Fieldbus, W = PROFIBUS PA, X = wireless, M = low-power 1–5 Vdc with HART |
| 5 | Process flange type and material | 2 = Coplanar, stainless steel; 3 = Coplanar, cast C-276; 4 = Coplanar, Alloy 400; 5 = Coplanar, plated carbon steel; 0 = alternate process connection |
| 6 | Isolating diaphragm | 2 = 316L stainless steel, 3 = Alloy C-276, 4 = Alloy 400, 5 = tantalum, 6 = gold-plated Alloy 400, 7 = gold-plated 316 stainless steel |
| 7 | O-ring | A = glass-filled PTFE, B = graphite-filled PTFE |
| 8 | Sensor fill fluid | 1 = silicone, 2 = inert |
| 9 | Housing material and conduit entry | A = aluminium, ½–14 NPT; B = aluminium, M20; J = stainless steel, ½–14 NPT; K = stainless steel, M20 |
| After 9 | Options | Bracket, display, hazardous-area approval, certificates and others |
Which pressure range does each range code give?
| Range code | 3051CD (differential) | 3051CG (gage) | 3051CA (absolute) |
|---|---|---|---|
| 0 | −3 to 3 inH2O (7.5 mbar) | not available | not available |
| 1 | −25 to 25 inH2O (62 mbar) | −25 to 25 inH2O | 0 to 30 psia (2.07 bar) |
| 2 | −250 to 250 inH2O (623 mbar) | −250 to 250 inH2O | 0 to 150 psia (10.3 bar) |
| 3 | −1000 to 1000 inH2O (2.49 bar) | −393 to 1000 inH2O | 0 to 800 psia (55.2 bar) |
| 4 | −300 to 300 psi (20.7 bar) | −14.2 to 300 psi | 0 to 4000 psia (275.8 bar) |
| 5 | −2000 to 2000 psi (137.9 bar) | −14.2 to 2000 psi | not available |
The range code gives the limits of the sensor. The calibrated span of a delivered transmitter is set inside those limits and is shown separately on the nameplate.
Which option codes appear most often?
| Option code | Meaning |
|---|---|
| B4 | Coplanar flange bracket, all stainless steel, for 2-inch pipe and panel mounting |
| M5 | LCD display |
| M4 | LCD display with local operator interface |
| E8 | ATEX flameproof and dust |
| I1 | ATEX intrinsic safety and dust |
| N1 | ATEX type n and dust |
| K8 | ATEX flameproof, intrinsic safety, type n and dust combined |
| E7 | IECEx flameproof and dust ignition-proof |
| I7 | IECEx intrinsic safety |
| E5 | FM explosion-proof and dust ignition-proof |
| I5 | FM intrinsically safe and nonincendive |
| Q4 | Calibration certificate |
| Q8 | Material traceability certification to EN 10204 3.1 |
| QT | Safety certified to IEC 61508 |
| T1 | Transient protection terminal block |
How is the example 3051CD2A22A1AB4 decoded?
The Emerson data sheet gives 3051CD 2 A 2 2 A 1 A B4 as a typical model number. Read position by position:
- 3051C: Coplanar pressure transmitter.
- D: differential pressure.
- 2: range −250 to 250 inH2O.
- A: 4–20 mA output with HART.
- 2: Coplanar stainless steel process flange.
- 2: 316L stainless steel isolating diaphragm.
- A: glass-filled PTFE O-ring.
- 1: silicone fill fluid.
- A: aluminium housing with ½–14 NPT conduit entries.
- B4: stainless steel mounting bracket.
Why does Alisios ask for the complete model code?
Two Rosemount 3051 transmitters that begin with the same characters can differ in range, output protocol, diaphragm material or hazardous-area approval. Each difference changes the part that is built and its price. Alisios quotes a Rosemount 3051 only from the complete model code on the nameplate, together with the serial number. The 3051T in-line and 3051L level transmitters follow the same principle with their own tables in the same data sheet.
Source: Emerson, Rosemount 3051 Pressure Transmitter product data sheet 00813-0100-4001. Emerson revises this data sheet and its option list. The current revision applies.
Have the equipment nameplate to hand?
Send a photo or the part number. We check the model and reply within 4 business hours.
Related pages
What does the D, G or A after 3051C mean?
It is the measurement type. 3051CD measures differential pressure, 3051CG measures gage pressure and 3051CA measures absolute pressure.
Is the range code the same as the calibrated range?
No. The range code fixes the limits of the sensor. The calibrated range is set within those limits when the transmitter is ordered or commissioned, and it is shown separately on the nameplate.
Which Rosemount 3051 option codes are ATEX and IECEx approvals?
In the Emerson data sheet, E8 is ATEX flameproof, I1 is ATEX intrinsic safety, N1 is ATEX type n, E7 is IECEx flameproof and I7 is IECEx intrinsic safety.